HOME Basic knowledge on ggypsumh Interior restrictions

List of interior restrictions (Building Standards Act Enforcement Ordinance, Articles 128, 129 and 112)

Land / structure / scale classification Total floor area of the portion to be used for the application Interior restrictions
In case of fire resistant building In case of quasi fire resistant building In case of other kinds of building Living space etc. Main corridor, stairway, aisle leading to the ground
1 Theater / movie theater / entertainment hall / audience space / public hall / meeting place (Audience seat)
400m2more
(Audience seat)
100m2more
Noncombustible material*
Quasi noncombustible material
Flame retardant material

(The ceiling of a room of a building having a living space on the third floor or higher floor intended for the purpose detailed in this section shall be noncombustible or quasi noncombustible.)
Noncombustible material
Quasi noncombustible material
2 Hospitals / clinics (with accommodation facilities for patients) / hotels / inns / lodging houses / dormitories / apartments / retirement houses / child welfare facilities etc.
(Refer to Building Standards Act Enforcement Ordinance Article 19 Clause 1)
(3 floors or more) 300m2 or more (except if compartmentalized with fire partition wall every 100m2 (or 200m2 in case of dwelling unit of an apartment), this also applies to the column to the right) (2 floors or more) 300m2 or more (Hospitals and clinics are limited only when there is a patient accommodation facility on the second floor) 200m2more
3 Department store / market / exhibition hall / cabaret / cafe / night club / ballet hall / dance hall / amusement center / public bath / waiting room / restaurant / eatery / commercial stores(Except 10m2 or less) (3 floors or more)
1000m2more
(2 floors or more)
500m2more
200m2more
4 In the living space in the ground floor or underground part of the building to be used for the purpose of 1.2.3 Entire floor area Noncombustible material
Quasi noncombustible material
5 Automobile garage / automobile repair shop Entire floor area
6 Windowless room for living area
(Refer to Building Standards Act Enforcement Ordinance Article 128 Clause 3 Item 2)
Entire floor area (except those with a ceiling height exceeding 6m)
7 Depending on the number of floors and the scale of the building
  • Those with number of floors of more than 3 and wider than 500m2
  • Those with number of floors of more than 2 and wider than 1000m2
  • Those with number of floors of more than 1 and wider than 3000m2
    However, the following are excluded:
  • Schools etc.
  • A living space compartmentalized with fire partition every 100m2 or less and does not serve the purpose of special buildings, and located at a height of 31m or less in the fire resistant or quasi fire resistant building
  • Parts of the building intended for the purposes specified in No. 2, with a height of 31m or less.
Noncombustible material*
Quasi noncombustible material
Flame retardant material
8 Room for indoor fire usage Housing: A room for indoor fire usage located on the floor other than the top floor in a building with number of floors of 2 or more Quasi noncombustible material |
Other than housing: all of the rooms for indoor fire usage (except those whose main structural parts are fire resistant structures) Quasi noncombustible material
9 Those with number of floors of 11 or more* 1
*1
Parts of the building compartmentalized with fire partition walls with an area of 100m2 or less |
Parts of the building compartmentalized with fire partition walls (excluding those with Type-B Fire Door) with an area of 200m2 or less Noncombustible material / quasi noncombustible material (also applies to the underground part of the building)
Parts of the building compartmentalized with fire partition walls with an area of 500m2 or less Noncombustible material (also applies to the underground part of the building)
10 Underground shopping area Parts of the building compartmentalized with fire partition walls with an area of 100m2 or less *2 Noncombustible material
(also applies to the underground part of the building)
Parts of the building compartmentalized with fire partition walls with an area of 200m2 or less Noncombustible material
Quasi noncombustible material
(also applies to the underground part of the building)*
Parts of the building compartmentalized with fire partition walls with an area of 500m2 or less Noncombustible material
(also applies to the underground part of the building)
11 Lobby for entering/exiting emergency elevator Entire floor area Noncombustible material (also applies to the underground part of the building)

1 According to the provisions of No. 9, no restrictions on the materials used are listed for parts compartmentalized with fire partition walls with an area of 100m2 or less. However, these restrictions are applicable to the provisions of No. 7 depending on the number of floors and the scale of the building.
2 According to the provisions of No. 10, no restrictions on the materials used are listed for parts compartmentalized with fire partition walls with an area of 100m2 or less. However, restrictions specified in No.4 are applicable to the parts of the building intended for purposes specified in No. 1, 2 and 3.

  • Part of the building subject to interior restrictions corresponds to parts facing the interior of walls and ceilings (or roof if ceiling is not present) in the living space, the main corridor leading from the living space to the ground, stairwell and other kinds of passageway. However, for parts marked with * in No. 1, 2, 3, 7, 9, 10, these restrictions does not apply to those with a height of 1.2 m or less from the floor of the wall of the living space corresponding to the provision.
    (Refer to Building Standards Act Enforcement Ordinance Article 129 Clause 1 and Article 112 Clause 6)
  • According to the provision of interior restrictions, the strictest provision shall apply to parts of buildings that fall under two or more provisions.
  • These provisions of interior restrictions are not applicable to parts of buildings provided with smoke eliminating equipment compliant to the provisions of Article 126 Clause 3 of Building Standards Act Enforcement Ordinance and automatic fire extinguishing equipment such as sprinklers, water spray type fire extinguishing equipment, foam type fire extinguishing equipment etc. (Building Standards Act Enforcement Ordinance Article 129 Clause 7)
  • Regarding the provisions of No. 9 and 10, the floor area of the fire partition compartment will be doubled for parts of the building equipped with automatic fire extinguishing equipment such as sprinklers, water spray type fire extinguishing equipment, foam type fire extinguishing equipment etc.
    (Building Standards Act Enforcement Ordinance Article 112 Clause 1)